/
Live Load Reduction

Live Load Reduction

Live Load Reduction Based on Alternative Method

Live load reduction is performed according to NYCBC - 2014 Chapter 16 Section 1607.9.2.

Live loads which are classified as “L,L_Heavy or L_Passenger” are permitted to be reduced in the alternative method.

Figure 4

The design live load of any structural member supporting 150 square feet or more is permitted to be reduced.

Reducible live load area is calculated as described below;

→ The tributary area of each column at column design line is determined.

→ The intersection area of the column tributary and the reducible load area is calculated at each floor.

→ Cumulative reducible area is calculated at each floor.

→ Reducible area of the transfer column ( if exists ) is multiplied by the distribution factor and added to cumulative reducible live load area at the transfer floor.

Live load reduction along column design line is calculated as follows;

→ Total reducible area of live load class L (if any) at each column is determined along the column design line as described before.

→ Reduction in percent is calculated based on the following equation;

R= 0.08*(At -150)

→ For one way slabs, tributary area, At, shall not exceed the product of slab span and a width normal to slab span of 0.5 times slab span.

→ Maximum reduction in percent can not be more than %23.1*(1+D/L) where D is dead load per square foot of area supported and L is unreduced live load per square foot of area supported.

L Load Reduction

Live loads not exceeding 100 psf and are other than public assembly or parking vehicle garages are classified as “L” live load.

→ Maximum reduction in percent for columns can not be more than %60.

→ Live load reduction factor is equal to maximum of (0.6, 1- Rmax/100).

L_Heavy Load Reduction

Live loads exceeding 100 psf are considered to be heavy live loads. Live load reduction for L_Heavy is calculated as follows;

→ If column supports 1 floor, live load reduction factor is 1.0

→ If column supports two or more floors, live load reduction factor is the maximum of ( 0.8, 1-Rmax/100 )

L_AssemblyGroupA Load Reduction

Live Loads which are classified as “L_AssemblyGroupA “ are not permitted to be reduced in alternative method. Thus live load reduction factor for L_AssemblyGroupA is always 1.0.

L_ParkingVehicleGarages Load Reduction

Live loads which are classified as “L_ParkingVehicleGarages” are permitted to be reduced as following;

→ If column supports 1 floor, live load reduction factor is 1.0

→ If column supports 2 or more floors, live load reduction factor is the maximum of (0.8, 1-Rmax/100).

Lr Load Reduction

Roof live loads which are classified as ”Lr” is considered to be unreducible live loads.

Go to library object : https://building.openbrim.org/objidr4f3vfupqplblac7wpk7r.libobj

Related content

Live Load Reduction Examples
Live Load Reduction Examples
More like this
Load Take Down
Load Take Down
More like this
Live Load Reduction Verification
Live Load Reduction Verification
More like this
Tributary
More like this
Load Rating Combination Table [PIG]
Load Rating Combination Table [PIG]
More like this
Load Rating Combination Table [CUG]
Load Rating Combination Table [CUG]
More like this